EasyManuals Logo

Fujitsu AOYG09KHCAN User Manual

Fujitsu AOYG09KHCAN
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #56 background imageLoading...
Page #56 background image
2-16. E: 94. Trip detection (Outdoor unit)
Indicator Indoor unit
Operation indicator 9 time flash
Timer indicator 4 time flash
Economy indicator Continuous flash
Error code E: 94
Detective actuator Outdoor unit
Main PCB Protection stop by over-current generation after inverter
compressor start processing completed generated
consecutively 10 times.
NOTE: The number of generations is reset when the
compressor starts up.
Compressor
Forecast of cause
Outdoor unit fan operation defective, foreign matter on
heat-exchanger, excessive rise of ambient temperature
Main PCB failure
Inverter compressor failure (lock, winding short)
Check point 1. Check the outdoor unit fan operation, heat-exchanger, ambient temperature
No obstructions in air passages?
Heat exchange fins clogged
Outdoor unit fan motor check
Ambient temperature not raised by the effect of other heat sources?
Discharged air not sucked in?
Check point 2. Replace main PCB
If Check point 1 do not improve the symptom, change main PCB.
Check point 3. Replace compressor
If Check point 2 do not improve the symptom, change compressor.
End
2-16. E: 94. Trip detection (Outdoor unit) - (03-20) - 2. Troubleshooting with error code
TROUBLESHOOTING
TROUBLESHOOTING

Table of Contents

Other manuals for Fujitsu AOYG09KHCAN

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AOYG09KHCAN and is the answer not in the manual?

Fujitsu AOYG09KHCAN Specifications

General IconGeneral
BrandFujitsu
ModelAOYG09KHCAN
CategoryAir Conditioner
LanguageEnglish

Related product manuals