- 74 -
DUCT TYPE
ARYG12-54LHTBP
5) Auto restart
Enables or disables automatic restart after a power interruption.
NOTE: Auto restart is an emergency function such as for power outage etc. Do not attempt to use
this function in normal operation. Be sure to operate the unit by remote controller or external
device.
6) Room temperature sensor switching
(Only for wired remote controller)
When using the wired remote controller temperature sensor, change the setting to "Both" (01).
00: Sensor on the indoor unit is active.
01: Sensors on both indoor unit and wired remote controller are active.
NOTE: Remote controller sensor must be turned on by using the remote controller.
7) Cold air prevention
This setting is to disable the cold air prevention function during heating operation. When disabled,
the fan setting will always follow the setting on the remote controller. (Excluding defrost mode)
8) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
10) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired
remote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
Function number Setting value Setting description Factory setting
40
00 Enable
01 Disable
Function number Setting value Setting description Factory setting
42
00 Indoor unit
01 Both
Function number Setting value Setting description Factory setting
43
00 Enable
01 Disable
Function number Setting value Setting description Factory setting
44
00 A
01 B
02 C
03 D
Function number Setting value Setting description Factory setting
46
00 Operation/Stop mode 1
01 (Setting prohibited)
02 Forced stop mode
03 Operation/Stop mode 2
Function number Setting value Setting description Factory setting
48
00 Both
01 Wired remote controller

Table of Contents