- 75 -
DUCT TYPE
ARYG12-54LHTBP
11) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
As the factory setting, this setting is initially activated.
Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for energy
saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
12) Switching functions for external output terminal
Functions of the external output terminal can be switched. For details, refer to “External input and
output”.
Function number Setting value Setting description Factory setting
49
00 Disable
01 Enable
02 Remote controller
Function number Setting value Setting description Factory setting
60
00 Operation status
01 - 08 (Setting prohibited)
09 Error status
10 Indoor unit fan operation status
11 External heater