4-3. Swing operation
To select vertical airflow swing operation
When the swing signal is received, the vertical airflow direction louver starts to swing.
Swinging range
Cooling mode/dry mode/fan mode (1 to 3): 1 ↔ 4
Heating mode/fan mode (4 to 6): 3 ↔ 6
When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
To select horizontal airflow swing operation
When the swing signal is received, the horizontal airflow direction louver starts to swing.
Swinging range
All mode: 1 ↔ 5
When the indoor fan is S-LOW or stop mode, the swing operation is interrupted and it stops at
either upper end or bottom end.
To select vertical and horizontal airflow swing operation
When the swing signal is received, both of the vertical and the horizontal airflow direction louver
start to swing.
4-3. Swing operation - (04-14) - 4. Louver control