7-14. Peak cut operation (for 34 model)
The current value is limited to reduce the power consumption by external input.
Peak cut level Level 1 Level 2 Level 3 Level 4
Peak cut for rated capacity
Forced thermostat
off
50% 75% 100%
NOTES:
•
During defrost operation, peak cut operation becomes invalid.
• Even during the peak cut operation, the operations of current overload, economy, and low noise
are effective and the outdoor unit operates by lowest current of them.
7-15. Outdoor unit low noise operation (for 34 model)
The compressor frequency and outdoor unit fan speed are limited to reduce the operation noise by
external input.
Low noise mode
Outdoor fan speed
Compressor
frequency
Sound level
rpm rps dB (A)
Level 1
Cooling/Dry 690 43
-2
Heating 690 49
Level 2
Cooling/Dry 690 30
-4
Heating 690 36
NOTES:
•
During the defrost operation, the compressor operates by the speed for defrost operation.
• Even during the low noise operation, the operations of current overload, economy, and peak cut
are effective and the outdoor unit operates by lowest current of them.
Capacity priority mode
• Operation condition
The function setting is set to 1.
• Capacity check condition
– Shortage: Compressor frequency > limited compressor frequency for low noise mode
– Enough: Compressor frequency ≤ limited compressor frequency for low noise mode
• Operation
When detecting the shortage capacity or enough capacity condition continuous 30 minutes, the
mode is changed as follows:
– Automatic switching 1 (Level 1 setting)
Enough for 30 min
Shortage for 30 min
Normal operationLow noise mode 1
– Automatic switching 2 (Level 2 setting)
Low noise
mode 2
Normal
operation
Low noise
mode 1
Enough for 30 min
Shortage for 30 min
Enough for 30 min
Shortage for 30 min
7-14. Peak cut operation (for 34 model) - (04-25) - 7. Various control