EasyManua.ls Logo

Fujitsu ASTG30KMTC - Current Release Control; Cooling Pressure Over-Rise Protection

Fujitsu ASTG30KMTC
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8-8. High temperature and high pressure release control
(
heating mode)
In heating mode, the compressor is controlled as follows.
¢ Model: AOTG30KMTC
Indoor unit heat exchanger
temperature rises
Indoor unit heat exchanger
temperature drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 63°C
BC: 55°C
CD: 53°C
DE: 50°C
Zone Operation
Zone A Compressor is stopped.
Zone B
The compressor frequency is decreased.
-15 rps/120 sec.
Zone C -2 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
¢ M
odel: AOTG34KMTC
Indoor unit heat exchanger
pressure rises
Indoor unit heat exchanger
pressure drops
Stable zone
AB
BC
CD
DE
Zone A
Zone B
Zone C
Zone D
Zone E
AB: 4.1 MPaG
BC: 3.5 MPaG
CD: 3.3 MPaG
DE: 3.0 MPaG
Zone Operation
Zone A Compressor is stopped.
Zone B
The compressor frequency is decreased.
-15 rps/120 sec.
Zone C -2 rps/120 sec.
Zone D
The protection is released and the operation is returned to normal mode.
Zone E
8-8. High temperature and high pressure release control (heating mode) - (04-29) - 8. Various protections
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Related product manuals