14) Outdoor temperature zone boundary temperature B
Setting required if changing of the outdoor temperature setting for heat pump only zone is required
when auxiliary heater control by outdoor temperature 1 is performed on the indoor unit. For details,
refer to Chapter 3-4. "Details of function" on page 05-20.
Function number Setting value Setting description Factory setting
67
00 6 °C
01 -10 °C
02 -8 °C
03 -6 °C
04 -4 °C
05 -2 °C
06 0 °C
07 2 °C
08 4 °C
09 6 °C
10 8 °C
11 10 °C
12 12 °C
13 14 °C
14 16 °C
15 18 °C
1-1. Function settings by using remote controller - (05-8) - 1. Function settings (For indoor unit)