Auxiliary heater control 1
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Off
Off
O
n
Tr-Ts ≥ -1°C
T
r-Ts
Tr-Ts (=Thon) < -3°C
Tr-Ts ≥ -10°C
Tr-Ts < -12°C
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
Example: When set temperature (Ts) is 22°C (Factory setting),
and room temperature (Tr) increases above 12°C, signal output is on.
and room temperature (Tr) increases above 21°C, signal output is off.
and room temperature (Tr) decreases below 19°C, signal output is on.
and room temperature (Tr) decreases below 10°C, signal output is off.
Auxiliary heater control 2
Operation Condition
Heater on Heater is on as shown in following diagram of heating temperature.
Heater off
Heater is off as shown in following diagram of heating temperature.
Other than heating mode
Error occurred
Forced thermostat off
Fan stop protection
Temperature of heater on (Thon): Adjustable by function number 62 (Operating temperature
switching of external heaters).
All control temperatures will shift by adjusting “Thon”.
Off
O
n
Tr-Ts ≥ -1°C
Tr-Ts
Tr-Ts (=Thon) < -3°C
Tr: Room temperature
Ts: Set temperature
Thon: Heater on temperature
3-4. Details of function - (05-26) - 3. External input and output (For indoor unit)
FIELD
WORKING
FIELD
WORKING