1-2. Outdoor unit
Type Inverter heat pump
Model name AOTG30KMTC AOTG34KMTC
Power supply 240 V ~ 50 Hz
Available voltage range 198—264 V
Starting current A 10.7 11.2
Fan
Airflow rate
Cooling
l/s (m
3
/h)
861 (3,100) 1,139 (4,100)
Heating 945 (3,400) 1,139 (4,100)
Type × Q'ty Propeller fan × 1
Motor output W 100 111
Sound pressure level *1
Cooling
dB (A)
50 50
Heating 54 54
Sound power level dB (A) 67 67
Heat exchanger
Dimensions
(H × W × D)
mm
798 × 900 × 36.4
Main1: 882 × 957 × 18.19
Main2: 882 × 927 × 18.19
Sub: 882 × 580 × 18.19
Fin pitch 1.30 1.45
Rows × Stages 2 × 38 Main: 2 × 42, Sub: 1 × 42
Pipe type Copper
Fin type
Type (Material) Corrugate (Aluminum)
Surface treatment Corrosion resistance (Blue fin)
Compressor
Type × Q'ty DC Twin rotary × 1
Motor output W 2,200
Refrigerant
Type R32
Charge g 1,650 2,000
Refrigerant oil
Type POE
Amount
cm
3
800
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10YR 7.5/1.0
Dimensions
(H × W × D)
Net
mm
830 × 900 × 330 914 × 970 × 370
Gross 1,000 × 1,050 × 445 1,078 × 1,064 × 479
Weight
Net
kg
60 74
Gross 68 83
Connection pipe
Size
Liquid
mm
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Pre-charge length
m
20 30
Max. length 75
Max. height difference 30
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
Drain hose
Material LDPE
Size mm Ø 13.0 (I. D.), Ø 16.0 to Ø 16.7 (O. D.)
International protection rating IPX4
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 27 °CDB/19 °CWB, and outdoor temperature of 35 °CDB/24 °CWB.
Heating: Indoor temperature of 20 °CDB/15 °CWB, and outdoor temperature of 7 °CDB/6 °CWB.
Pipe length: 7.5 m, Height difference: 0 m.
Protective function might work when using it outside the operation range.
*1: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-1. Indoor unit - (01-2) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASTG30KMTC and is the answer not in the manual?

Fujitsu ASTG30KMTC Specifications

General IconGeneral
BrandFujitsu
ModelASTG30KMTC
CategoryAir Conditioner
LanguageEnglish

Related product manuals