2-2. Mini duct type
Model name ARYG07LSLAP ARYG09LSLAP ARYG12LSLAP
Power supply 1Ø 230 V ~50 Hz
Available voltage range 198—264 V
Capacity kW class 2.0 2.5 3.5
Input power Fan
HIGH
W
33 40 47
MED 23 23 26
LOW 20 20 22
QUIET 18 18 18
Running current A 0.29 0.33 0.38
Fan
Airflow rate
Cooling
HIGH
m
3
/h
550 600 650
MED 440 450 490
LOW 390 400 430
QUIET 360 360 360
Heating
HIGH 550 600 650
MED 440 450 490
LOW 390 400 430
QUIET 360 360 360
Type × Q'ty Sirocco fan × 2
Motor output W 75
Recommended static pressure Pa 0 to 30
Sound pressure level *
Cooling
HIGH
dB (A)
29 29 31
MED 26 26 27
LOW 24 24 25
QUIET 23 23 23
Heating
HIGH 29 29 31
MED 26 26 27
LOW 24 24 25
QUIET 23 23 23
Sound power level
Cooling
dB (A)
52 54 55
Heating 53 56 57
Heat exchanger type
Dimensions (H × W × D) mm 336 × 490 × 26.6
Fin pitch mm 1.3
Rows × Stages 2 × 16
Pipe type Copper tube
Fin type Aluminum
Enclosure
Material Steel sheet
Color —
Dimensions
(H × W × D)
Net
mm
198 × 700 × 450
Gross 250 × 930 × 580
Weight
Net
kg
15.5
Gross 19.5
Connection
pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas Ø9.52 (Ø3/8)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Drain hose
Material Hard PVC
Size mm Ø 25 (I.D.), Ø 32 (O.D.)
Remote controller type Wired (Wireless [option])
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 10 Pa
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.