11. Safety devices
Type of protection Protection form
Model
AOYG09KMCDN AOYG12KMCDN AOYG14KMCDN
Circuit protection Current fuse (Main PCB)
250 V, 25 A
250 V, 5 A
Fan motor
protection
Thermal protection
Activate
103±18 °C
Fan motor stop
125±10 °C
Fan motor stop
Reset
95±18 °C
Fan motor restart
120±10 °C
Fan motor restart
Compressor
protection
Terminal protection
program
(Discharge temp.)
Activate
110 °C
Compressor stop
Reset
After 7 minutes
Compressor restart
Thermal protection
program
(Outdoor temp.)
(Only in COOL or DRY
mode)
Activate
-15 °C
Compressor stop
Reset
-10 °C
Compressor restart
- 60 -