01 - 41
-
CASSETTE TYPE
AU
G12-24LVL
CASSETTE TYPE
AU
G12-24LVL
4) Cooler room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be selected as shown in the table below.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Standard
30
00
Slightly lower control 01
Lower control 02
Warmer control 03
5) Heater room temperature correction
Depending on the installed environment, the room temperature sensor may require a correction.
The settings may be changed as shown in the table below.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Standard
31
00
Lower control 01
Slightly warmer control 02
Warmer control 03
6) Auto restart
Enable or disable automatic system restart after a power outage.
(
. . .Factory setting)
Setting Description Function Number Setting Value
Yes
40
00
No 01
* Auto restart is an emergency function such as for power failure etc. Do not start and stop the indoor unit by this
function in normal operation. Be sure to operate using the remote controller,or external input device.
7) Indoor room temperature sensor switching function
(Only for Wired remote controller)
The following settings are needed when use the control by Wired remote controller temperature
sensor.
(
. . .Factory setting)
Setting Description Function Number Setting Value
No
42
00
Yes 01
If setting value is “00”,
•
room temperature is controlled by the indoor unit temperature sensor.
If setting value is “01”,
•
room temperature is controlled by either indoor unit temperature sensor or remote controller unit sensor.
8) Remote controller signal code
Change the indoor unit Signal Code,depending on the remote controllers.
Setting Description Function Number Setting Value
A
44
00
B 01
C02
D03
9) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
(
. . . Factory setting)
Setting description Function number Setting value
Operation/Stop mode
46
00
(Setting forbidden) 01
Forced stop mode 02