EasyManua.ls Logo

Fujitsu AUUH18LUAS - Page 11

Fujitsu AUUH18LUAS
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1-2. Outdoor unit
Type Inverter, Heat pump
Model name AOUH18LUAS1 AOUH24LUAS1
Power supply 208/230 V~ 60 Hz
Power supply intake Outdoor unit
Available voltage range 187—253 V
Starting current A 8.1 10.3
Fan
Airflow rate
Cooling
CFM (m
3
/h)
1,395 (2,370) 2,187 (3,715)
Heating 1,460 (2,480) 2,187 (3,715)
Type × Qty Propeller fan × 1
Motor output 49 100
Sound pressure level*
Cooling
dB (A)
52
Heating 55 54
Heat exchanger type
Dimensions
(H × → × D)
in (mm)
Main 1: 23-1/8 × 34-11/16 × 11/16
(588 × 881 × 18.19)
Main 2: 23-1/8 × 33-1/2 × 11/16
(588 × 851 × 18.19)
Main 1: 29-3/4 × 35-5/8 × 11/16
(756 × 905 × 18.19)
Main 2: 29-3/4 × 35-5/8 × 11/16
(756 × 905 × 18.19)
Fin pitch FPI
Main 1: 20
Main 2: 20
Main 1: 18
Main 2: 18
Rows × Stages
Main 1: 1 × 28
Main 2: 1 × 28
Main 1: 1 × 36
Main 2: 1 × 36
Pipe type Copper tube
Fin type
Type (Material) Aluminum
Surface treatment PC fin Blue fin
Compressor
Type DC rotary DC twin rotary
Motor output 1,030 1,360
Refrigerant
Type R410A
Charge
lb oz 2 lb 12 oz 4 lb 10 oz
g 1,250 2,100
Refrigerant oil
Type POE (RB68)
Amount
in
3
(cm
3
)
24.4 (400) 48.8 (800)
Enclosure
Material Steel sheet
Color
Beige
Approximate color of Munsell 10↔R 7.5/1.0
Dimensions
(H × → × D)
Net
in (mm)
24-7/8 × 31-7/16 × 11-7/16
(632 × 799 × 290)
31 × 37 × 12-5/8
(788 × 940 × 320)
Gross
27-1/4 × 37 × 14-3/4
(692 × 940 × 375)
38-1/16 × 40-7/16 × 17-1/2
(966 × 1,027 × 445)
→eight
Net
lb (kg)
86 (39) 117 (53)
Gross 95 (43) 134 (61)
Connection pipe
Size
Liquid
in (mm)
Ø1/4 (Ø6.35) Ø3/8 (Ø9.52)
Gas Ø1/2 (Ø12.70) Ø5/8 (Ø15.88)
Method Flare
Pre-charge length
ft (m)
66 (20)
Max. length 98 (30) 164 (50)
Max. height difference 49 (15) 98 (30)
Operation range
Cooling
°F (°C)
14 to 115 (-10 to 46) -5 to 115 (-21 to 46)
Heating -5 to 75 (-21 to 24)
Drain hose
Material LDPE
Tip diameter in (mm)
Ø1/2 (Ø13.0) (I.D.)
Ø5/8 to Ø11/16 (Ø16.0 to Ø16.7) (O.D.)
NOTES:
Specifications are based on the following conditions:
Cooling: Indoor temperature of 80°FDB (26.67°CDB)/67°F→B (19.44°C→B), and outdoor temperature of 95°FDB (35°CDB)/75°F→B (23.9°C→B).
Heating: Indoor temperature of 70°FDB (21.11°CDB)/60°F→B (15.56°C→B), and outdoor temperature of 47°FDB (8.33°CDB)/43°F→B (6.11°C→B).
Pipe length: 25 ft (7.5 m), Height difference: 0 ft (0 m). (Between outdoor unit and indoor unit.)
Protective function might work when using it outside the operation range.
*: Sound pressure level
Measured values in manufacturer’s anechoic chamber.
Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-2. Outdoor unit - (01-5) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION

Table of Contents

Related product manuals