5) Room temperature control for indoor unit sensor
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
→hen the temperature of the room temp. sensor is 78°F and the setting value is “03” (-2°F),
the corrected temp. will be 80°F (78°F - [-2°F]).
The temperature correction values show the difference from the Standard setting “00” (manufactur-
er’s recommended value).
Function number Setting value Setting description
Factory
setting
30
(For cooling)
31
(For heating)
00 Standard setting ♦
01 No correction 0.0°F (0.0°C)
02 -1°F (-0.5°C)
More cooling
Less heating
03 -2°F (-1.0°C)
04 -3°F (-1.5°C)
05 -4°F (-2.0°C)
06 -5°F (-2.5°C)
07 -6°F (-3.0°C)
08 -7°F (-3.5°C)
09 -8°F (-4.0°C)
10 +1°F (+0.5°C)
Less cooling
More heating
11 +2°F (+1.0°C)
12 +3°F (+1.5°C)
13 +4°F (+2.0°C)
14 +5°F (+2.5°C)
15 +6°F (+3.0°C)
16 +7°F (+3.5°C)
17 +8°F (+4.0°C)
1-1. Function settings by using remote controller - (05-3) - 1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING