EasyManuals Logo
Home>Fujitsu>Air Conditioner>Ceiling Type

Fujitsu Ceiling Type Design & Technical Manual

Fujitsu Ceiling Type
343 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #143 background imageLoading...
Page #143 background image
9. Electrical characteristics
Indoor unit Power supply
Wiring specification *
1
(Total *
2
)
Type Model name
Frequency
(Hz)
Voltage
(V)
MCA
(A)
Connection cable (mm
2
)
Compact
cassette
AUYG18LVLB 0.2
AUYG22LVLA 0.3
AUYG24LVLA 0.3
Cassette
AUYG30LRLE 0.7
AUYG36LRLE 0.7
AUYG45LRLA 1.2
Slim duct ARYG18LLTB 0.5
Duct
ARYG22LMLA 0.7
ARYG24LMLA 230 50 0.7 1.5
ARYG30LMLE 2.0
ARYG36LMLE 2.0
ARYG45LMLA 2.1
Floor/
Ceiling
ABYG18LVTB 0.5
ABYG22LVTA 0.7
ABYG24LVTA 0.7
Ceiling
ABYG30LRTE 0.7
ABYG36LRTE 0.7
ABYG45LRTA 0.8
MCA: Minimum Circuit Amperes = Maximum operating current (Full load)
NOTES:
• *1: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005.
As the regulations of wire size and circuit breaker differ in each country or region, select appro-
priate devices complied to the regional standard.
• *2: Total length of all wirings that interconnect between indoor units and between indoor unit
and outdoor unit.
- 135 -
9. Electrical characteristics
INDOOR UNITS
SIMULTANEOUS
MULTI
INDOOR UNITS
SIMULTANEOUS
MULTI

Table of Contents

Other manuals for Fujitsu Ceiling Type

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu Ceiling Type and is the answer not in the manual?

Fujitsu Ceiling Type Specifications

General IconGeneral
BrandFujitsu
ModelCeiling Type
CategoryAir Conditioner
LanguageEnglish

Related product manuals