Model name ARYG30LMLE ARYG36LMLE ARYG45LMLA
Power supply 1Ø 230 V ~50 Hz
Available voltage range 198—264 V
Fan
Airflow rate
Cooling
HIGH
m
3
/h
1,900 2,100
MED 1,620 1,750
LOW 1,270 1,350
QUIET 980 1,070
Heating
HIGH 2,100 2,100
MED 1,620 1,750
LOW 1,270 1,350
QUIET 980 1,070
Type × Q'ty Sirocco fan × 2
Motor output W 197
Recommended static pressure Pa 30 to 150
Sound pressure level *
Cooling
HIGH
dB (A)
39 42
MED 35 38
LOW 30 32
QUIET 26 28
Heating
HIGH 42 42
MED 35 38
LOW 30 32
QUIET 26 28
Heat exchanger type
Dimensions (H × W × D) mm 294 × 1,000 × 39.9 294 × 1,000 × 53.2
Fin pitch mm 1.40
Rows × Stages 3 × 14 4 × 14
Pipe type Copper
Fin type Aluminum
Enclosure
Material Steel sheet
Color —
Dimensions
(H × W × D)
Net
mm
270 × 1,135 × 700
Gross 300 × 1,320 × 790
Weight
Net
kg
40
Gross 47
Connection
pipe
Size
Liquid
mm (in)
Ø 9.52 (Ø 3/8)
Gas Ø 15.88 (Ø 5/8)
Method Flare
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Drain hose
Material Steel
Size mm Ø35.7 (I.D.), Ø38.1 (O.D.)
Remote controller type Wired (Wireless [option])
NOTES:
• Values mentioned in the table are based on the following conditions:
– Static pressure: 47 Pa (30, 36 model), 60 Pa (45 model)
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
- 7 -
2-4. Duct type 2. Specifications
INDOOR UNITS
SIMULTANEOUS
MULTI
INDOOR UNITS
SIMULTANEOUS
MULTI