4. Connect the cable to the terminals on the front case.
Fix the cable together with the sheath with the cable tie. Cut off the excess cable tie.
Tightening torque
Terminal screw 0.8 to 1.2 N•m
1. 12V (Red)
2. Signal (White)
3. COM (Black)
Cable tie
Remote controller
cable (sheath)
Hole for cable tie
2 mm
Good Prohibited
To avoid an excessive tension or pressure to the terminal block,
fix the remote controller cable with the cable tie properly.
CAUTION
• Be careful to avoid breaking the cable by over-tightening the cable tie.
• When connecting the remote controller cables, do not over-tighten the screws.
- 254 -
7-5. Wired remote controller (UTY-RVNYM: Optional part) 7. Remote controller