● For Direct (No Power Distribution Unit) Connections
The following diagram shows a power supply connection example when no power distribution units are used.
Figure 11 Example of a Power Supply Connection When a Power Distribution Unit Is Not Used
Line 0 Line 1
CP CP
PSU
PSU
PSU
PSU
ETERNUS AF
↓ To power supply facility
Distribution board
Drive enclosure
Controller
enclosure
Distribution board
↑ To power supply facility
PSU: Power Supply Unit
CP: Circuit Protector
•
Only connect the ETERNUS AF to circuit protectors.
Input Power Supply Lines
Multiple power supply facilities in the building or multiple UPS units are recommended for power supply redun-
dancy. A redundant configuration is used for the power supply of the
ETERNUS AF. Business can continue even if
one of the power supply lines fails.
However, a single power supply facility configuration is also allowed for the entire system optimization (includ-
ing the server). When selecting a single configuration, take into consideration the availability of the system.
Figure 12 Dual-Line Power Supply (When Connecting to Power Sockets)
Power supply
facility
Power supply
facility
PSU
PSU
ETERNUS AF
Power distribution unit
Line 0
Line 1
1. ETERNUS AF Installation
Outlet/Socket Specifications
28
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AG-1812-06ENZ0