EasyManua.ls Logo

Fujitsu ETERNUS AF250 S2 - Table 2 Efficiency and Power Factor of the Power Supply Unit (ETERNUS AF250 S2)

Fujitsu ETERNUS AF250 S2
38 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Item ETERNUS AF250 S2
Environmental conditions Temperature Operating 10 – 40°C
Not operating 0 – 50°C
Shipping -40 – 60°C
Temperature gradient 15°C/Hr or less
Humidity Operating 20 – 80%RH
Not operating 8 – 80%RH
Shipping 8 – 90%RH
Humidity gradient 30%/day or less
Maximum wet bulb temperature 29°C
Altitude above sea level 0 – 3,000m
Airborne dust
0.15mg/m
3
or less
Gas concentration tolerance level Cl
2
: 6.8ppb or less, H
2
S: 7.1ppb or less,
SO
2
: 37ppb or less, NH
3
: 423.5ppb or less,
NO
2
: 52ppb or less, O
3
: 5ppb or less,
HCl: 6.6ppb or less, HF: 3.6ppb or less
Oil vapor
0.2mg/m
3
or less
Seawater (salt corrosion) If the ETERNUS AF is installed on the ocean or
premises within 0.5km from the coast, neces-
sary measures must be taken to prevent salt
corrosion.
Vibration limit Operating 400gal
Not operating 1,000gal
Noise emission (*8) Sound pressure level 47dB (A)
Sound power level 6.5B
*1: For power distribution units, there are multiple types of exteriors. For details, refer to "
Specifications for
Optional Power Supply Products" (page 18).
*2: These values are for product ID ETFP4BU-L.
*3: These values are for product ID ETFP4DU-L.
*4: A 2U power distribution unit is composed of two 1U power distribution units.
*5: These values are for product ID ETFP16U-L / ETFP12U-L.
*6: These values are for product ID ETFP48U-L / ETFP32U-L.
*7: These values are for each enclosure when 24 drives are installed.
*8: These values are measured when a single controller enclosure and a single drive enclosure are configured
in an environment in which the temperature is 23
± 2°C at 0 meters above sea level.
Table 2 Efficiency and Power Factor of the Power Supply Unit (ETERNUS AF250 S2)
Component name
80PLUS
®
Efficiency
Power fac-
tor
Output
20% (*1) 50% (*1) 100% (*1) 50% (*1)
Controller enclosure GOLD (*2) 89.3% 92.5% 90.2% 0.975 Multiple output
Drive enclosure 89.3% 92.5% 90.2% 0.975
*1: Indicates the rated load against the rated output of the PSU.
1. ETERNUS AF Installation
Installation Specifications
8
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AG-1812-06ENZ0

Table of Contents

Other manuals for Fujitsu ETERNUS AF250 S2

Related product manuals