1. ETERNUS AF Installation
This chapter provides the installation specification of the ETERNUS AF.
Installation Specifications
ETERNUS AF250 S2
Table 1 shows the installation specifications of the ETERNUS AF250 S2 and Table 2 shows the efficiency and the
power factor of the power supply unit.
Table 1 ETERNUS AF250 S2 Installation Specifications
Item ETERNUS AF250 S2
Dimensions
(W ´ D ´ H)
Controller enclosure
482 ´ 645 ´ 88mm (2U)
Drive enclosure
482 ´ 540 ´ 88mm (2U)
Power distribution unit
(*1)
1U
435 ´ 148 ´
38mm (*2),
482 ´ 111 ´ 44mm (*3)
2U (*4)
(485 ´
280 ´ 43mm) ´ 2 (*5),
(485 ´ 123 ´ 44mm) ´ 2 (*6)
Maximum weight (*7) Controller enclosure 35kg
Drive enclosure 35kg
Power distribution unit
(*1)
1U 2.0kg (*2),
2.5kg (*3)
2U (*4)
(6.0kg) ´
2 (*5),
(3.0kg) ´ 2 (*6)
Power Voltage AC 100 – 120V, AC 200 – 240V
Phase Single
Frequency 50Hz/60Hz
Maximum power con-
sumption (*7)
Controller enclosure AC 100 – 120V 850W (860VA)
AC 200 – 240V 850W (860VA)
Drive enclosure AC 100 – 120V 430W (440VA)
AC 200 – 240V 430W (440VA)
Maximum heat genera-
tion (*7)
Controller enclosure AC 100 – 120V 3,100kJ/h
AC 200 – 240V 3,100kJ/h
Drive enclosure AC 100 – 120V 1,600kJ/h
AC 200 – 240V 1,600kJ/h
Maximum amount of ex-
haust air
Controller enclosure
4.0m
3
/min
Drive enclosure
4.0m
3
/min
7
FUJITSU Storage ETERNUS AF250 S2, ETERNUS AF250 All-Flash Arrays
Site Planning Guide
Copyright 2021 FUJITSU LIMITED
P3AG-1812-06ENZ0