IDL 101
SPECIFICATION
86
HB_IDL101_E_V222.doc
Gantner Instruments Test & Measurement GmbH
11. SPECIFICATIONS
11.1. Power Supply
Voltage range: +10 .. 30 VDC
Power input: approx. 1W
Internal protection: Integrated, Reversible Protection Against Excess Voltage, Excess Current and
Wrong Polarity Connection
11.2. Signal Inputs/Outputs
Analog inputs: 6
Analog outputs: 1
Digital inputs/outputs: 16 (direction selectable)
11.3. Signal Processing
Sampling rate: Fast“ (0s), 1s, 2s, 3s, 4s, 5s, 10s, 20s, 30s or 60 s selectable
A/D-Converter: 10 Bit
11.4. Analog Inputs (6 per Module)
Voltage range: 0..10V / 0..1V / ± 50mV
Resistance range: 0..2000
Ω /
80..200
(Pt 100)
11.4.1. Measurement of Voltage
Measuring principle: single-ended, differential
Numbers: max. 6
Input impedance: 10 M
Measurement of Voltage
Range Inaccuracy
(1)
Resolution
(1)
Noise
(1)
Linearity error
(2)
Temperature drift
(2)
0..10 V 0,2 % 0,1 %
0..1 V 0, 1 % 50 ppm/°C
± 50 mV 0,3 % 0,2 %
(1) Data for T=20°C and 80% of the measuring range, (2) Data based on component specifications.