IDL 101
SPECIFICATION
HB_IDL101_E_V222.doc
87
Gantner Instruments Test & Measurement GmbH
11.4.2. Measurement of Current
□
Measuring principle: -
□
Numbers: max. 6
□
Input impedance: external
Measurement of Current
Range Inaccuracy
(1)
Resolution
(1)
Noise
(1)
Linearity error
(2)
Temperature drift
(2)
0..20 mA 0,2 % 0,1 % 0, 1 % 50 ppm/°C
(1) Data for T=20°C and 80% of the measuring range, (2) Data based on component specifications.
All values valid after a warm up phase of 15 minutes. The percentage correspondent to the measuring range.
11.4.3. Measurement of Resistance
□
Measuring principle: 2- and 4- wire
□
Numbers: max. 6
□
Measuring current: 0,5 mA
□
Measuring Range : Pt100 (-40°C .. +60°C)
Pt100 (-60°C .. +250°C)
Measurement of Resistance
Range Inaccuracy
(1)
Resolution
(1)
Noise
(1)
Linearity error
(2)
Temperature drift
(2)
2000
Ω
0,3 % 0,1 % 0,2 % 50 ppm/°C
(1) Data for T=20°C and 80% of the measuring range, (2) Data based on component specifications.
All values valid after a warm up phase of 15 minutes. The percentage correspondent to the measuring range.
11.5. Analog Output (1 per Module)
Output Voltage: 0 .. 10 V
Accuracy: 0.5 %
Resolution: 40 mV
Swing-In-Time: 10 ms