IDL 101
SPECIFICATION
88
HB_IDL101_E_V222.doc
Gantner Instruments Test & Measurement GmbH
11.6. Digital Inputs/Outputs (6 per Module)
as Input:
Function: Status, frequency, counter
Input voltage: max. +30 VDC
Input current: max. 1,5 mA
Input frequency: max. 2 kHz (I/O 01 .. I/O 06)
max. 100Hz (I/O 01 .. I/O 16)
Logic state: Low-Active
Threshold low: > +3,5 VDC (“0“)
Threshold high: < +1,0 VDC (“1“)
as Output:
Function: Host out, process out
Output voltage: max. 30 VDC
Output current: max. 100 mA
Output frequency: max. 100 Hz
Output state: Open collector
11.7. Interfaces
Base: RS 485, RS 232
Data format: adjustable 8E1 / 8N1
Protocol: ASCII,
PROFIBUS according to DIN 19245, part 1
MODBUS according to PI-MBUS-300 Rev.D
Baud rate ASCII: 2.400 / 4.800 / 9.600 / 19.200 / 38.400 bps
Baud rate Modbus: 2.400 / 4.800 / 9.600 / 19.200 / 38.400 bps
Baud rate PROFIBUS: 9.600 / 19.200 bps
11.8. Operating Conditions
Ambient temperature: -30 to +60 °C
Storing temperature: -40 to +85 °C
Humidity: 0 to 95 % at +50 °C, non condensing