EasyManua.ls Logo

Gantner IDL 101 - Digital Inputs;Outputs (6 Per Module)

Default Icon
100 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
IDL 101
SPECIFICATION
88
HB_IDL101_E_V222.doc
Gantner Instruments Test & Measurement GmbH
11.6. Digital Inputs/Outputs (6 per Module)
as Input:
□
Function: Status, frequency, counter
□
Input voltage: max. +30 VDC
□
Input current: max. 1,5 mA
□
Input frequency: max. 2 kHz (I/O 01 .. I/O 06)
max. 100Hz (I/O 01 .. I/O 16)
□
Logic state: Low-Active
□
Threshold low: > +3,5 VDC (“0“)
□
Threshold high: < +1,0 VDC (“1“)
as Output:
□
Function: Host out, process out
□
Output voltage: max. 30 VDC
□
Output current: max. 100 mA
□
Output frequency: max. 100 Hz
□
Output state: Open collector
11.7. Interfaces
□
Base: RS 485, RS 232
□
Data format: adjustable 8E1 / 8N1
□
Protocol: ASCII,
PROFIBUS according to DIN 19245, part 1
MODBUS according to PI-MBUS-300 Rev.D
□
Baud rate ASCII: 2.400 / 4.800 / 9.600 / 19.200 / 38.400 bps
□
Baud rate Modbus: 2.400 / 4.800 / 9.600 / 19.200 / 38.400 bps
□
Baud rate PROFIBUS: 9.600 / 19.200 bps
11.8. Operating Conditions
□
Ambient temperature: -30 to +60 °C
□
Storing temperature: -40 to +85 °C
□
Humidity: 0 to 95 % at +50 °C, non condensing