13-18-609 Page 18
2-6
Electrical Wire Routing – Routing of the electrical power wires into the electrical hardware enclosure is
best done through its roof area.
Line Reactor – A line reactor provides conditioning of the electrical power supply to the compressor
package by attenuating noise and fluctuations. It shall be required in your particular application if any of
the following conditions exist:
· Transformer KVA is greater than recommended – see Figure 2-3, page 18.
· Line has switched Power Factor correction capacitors.
· Existing line reactor not properly sized – see Figure 2-3, page 18.
· Other large loads on the same power feed as the compressor.
GD Model
Volts
VFD HP RATINGS
Max KVA
GD Part Number
VS80 400/480 107 1000 90500142
VS80 575 107 1000 90500141
VS110 400/480 147 1500 90500144
VS110 575 147 1000 90500142
Figure 2- 3 – LINE REACTOR SIZING RECOMMENDATIONS
GROUNDING – Equipment must be properly grounded in accordance with the National Electrical Code
and/or applicable local codes.
`
Failure to properly ground the compressor package could result in injury or death.
Install ground wiring in accordance with the National Electrical Code and any
applicable local codes.
MOTOR LUBRICATION - Long time satisfactory operation of an electric motor depends in large measure
on proper lubrication of the bearings. Refer to Section 13, page 75 of this manual for complete motor
lubrication specifications and details.