1 INTRODUCTION 1.2 SPECIFICATIONS
1
NEUTRAL OVERVOLTAGE (FUNDAMENTAL)
Pick-up Level: 2.0 to 100.0 V secondary in steps of 0.01
Time Delay: 0.1 to 120.0 s in steps of 0.1
Pickup Accuracy: as per Neutral Volta
g
e Input
Timin
g
Accuracy: ±100 ms or ±0.5% of total time
Elements: Trip and Alarm
NEUTRAL UNDERVOLTAGE (3RD HARMONIC)
Blockin
g
Si
g
nals: Low power and low volta
g
e if open delta
Pick-up Level: 0.5 to 20.0 V secondary in steps of 0.01
if open delta VT; adaptive if wye VT
Time Delay: 5 to 120 s in steps of 1
Pickup Accuracy:
at ≤20.0 V secondary: as per Neutral Volta
g
e Input
at >20.0 V secondary: ±5% of pickup
Timin
g
Accuracy: ±3.0 s
Elements: Trip and Alarm
LOSS OF EXCITATION (IMPEDANCE)
Pickup Level: 2.5 to 300.0 Ω secondary in steps of 0.1
with adjustable impedance offset 1.0 to
300.0 Ω secondary in steps of 0.1
Time Delay: 0.1 to 10.0 s in steps of 0.1
Pickup Accuracy: as per Volta
g
e and Phase Current Inputs
Timin
g
Accuracy: ±100 ms or ±0.5% of total time
Elements: Trip (2 zones usin
g
impedance circles)
DISTANCE (IMPEDANCE)
Pickup Levels: 0.1 to 500.0 Ω secondary in steps of 0.1
50 to 85° reach in steps of 1
Time Delay: 0.0 to 150.0 s in steps of 0.1
Pickup Accuracy: as per Volta
g
e and Phase Current Inputs
Timin
g
Accuracy: 150 ms ±50 ms or ±0.5% of total time
Elements: Trip (two trip zones)
REACTIVE POWER
Block From Online: 0 to 5000 s in steps of 1
Pick- up Level: 0.02 to 1.50 × rated Mvar
(positive and ne
g
ative)
Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy: see power meterin
g
Timin
g
Accuracy: ±100ms or ±0.5% of total time
Elements: Trip and Alarm
REVERSE POWER
Block From Online: 0 to 5000 s in steps of 1
Pick- up Level: 0.02 to 0.99 × rated MW
Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy: see power meterin
g
Timin
g
Accuracy: ±100 ms or ±0.5% of total time
Elements: Trip and Alarm
LOW FORWARD POWER
Block From Online: 0 to 15000 s in steps of 1
Pick- up Level: 0.02 to 0.99 × rated MW
Time Delay: 0.2 to 120.0 s in steps of 0.1
Pickup Accuracy: see power meterin
g
Timin
g
Accuracy: ±100 ms or ±0.5% of total time
Elements: Trip and Alarm
PULSE OUTPUT
Parameters: + kwh, +kvarh, -kvarh
Interval: 1 to 50000 in steps of 1
Pulse Width: 200 to 1000 ms in steps of 1 ms
RTDS 1 TO 12
Pickup: 1 to 250°C in steps of 1
Pickup Hysteresis: 2°C
Time Delay: 3 sec.
Elements: Trip and Alarm
OVERLOAD / STALL PROTECTION / THERMAL MODEL
Overload Curves: 15 Standard Overload Curves
Custom Curve
Volta
e Dependent Custom Curve
(all curves time out a
ainst avera
e
phase current)
Curve Biasin
g
: Phase Unbalance
Hot/Cold Curve Ratio
Stator RTD
Online Coolin
Rate
Offline Coolin
Rate
Line Volta
e
Overload Pickup: 1.01 to 1.25
Pickup Accuracy: as per Phase Current Inputs
Timin
g
Accuracy: ±100 ms or ±2% of total time
Elements: Trip and Alarm
OTHER FEATURES
Serial Start/Stop Initiation
Remote Reset (Confi
g
urable Di
g
ital Input)
Test Input (Confi
g
urable Di
g
ital Input)
Thermal Reset (Confi
g
urable Di
g
ital Input)
Dual Setpoints
Pre-Trip Data
Event Recorder
Waveform Memory
Fault Simulation
VT Failure
Trip Counter
Breaker Failure
Trip Coil Monitor
Generator Runnin
g
Hours Alarm
IRIG-B Failure Alarm
ENVIRONMENTAL
Ambient Operatin
g
Temperature: –40°C to +60°C
Ambient Stora
g
e Temperature: 40°C to +80°C.
Humidity: Up to 90%, noncondensin
.
Altitude: Up to 2000 m
Pollution De
g
ree: 2
It is recommended that the 489 be powered up
at least once per year to prevent deterioration
of electrolytic capacitors in the power supply.
WARNING

Table of Contents

Other manuals for GE 489

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE 489 and is the answer not in the manual?

GE 489 Specifications

General IconGeneral
BrandGE
Model489
CategoryRelays
LanguageEnglish

Related product manuals