GE Power Management
489 Generator Management Relay 6-17
6 COMMUNICATIONS 6.3 MEMORY MAP
6
0643 RTD #4 MAX. TEMP. –52 to 251 1 °F F4 –52
0644 RTD #5 MAX. TEMP. –52 to 251 1 °F F4 –52
0645 RTD #6 MAX. TEMP. –52 to 251 1 °F F4 –52
0646 RTD #7 MAX. TEMP. –52 to 251 1 °F F4 –52
0647 RTD #8 MAX. TEMP. –52 to 251 1 °F F4 –52
0648 RTD #9 MAX. TEMP. –52 to 251 1 °F F4 –52
0649 RTD #10 MAX. TEMP. –52 to 251 1 °F F4 –52
064A RTD #11 MAX. TEMP. –52 to 251 1 °F F4 –52
064B RTD #12 MAX. TEMP. –52 to 251 1 °F F4 –52
LEARNED DATA / ANALOG IN MIN/MAX
0700 ANALOG INPUT 1 MINIMUM –50000 to 50000 1 Units F12 0
0702 ANALOG INPUT 1 MAXIMUM –50000 to 50000 1 Units F12 0
0704 ANALOG INPUT 2 MINIMUM –50000 to 50000 1 Units F12 0
0706 ANALOG INPUT 2 MAXIMUM –50000 to 50000 1 Units F12 0
0708 ANALOG INPUT 3 MINIMUM –50000 to 50000 1 Units F12 0
070A ANALOG INPUT 3 MAXIMUM –50000 to 50000 1 Units F12 0
070C ANALOG INPUT 4 MINIMUM –50000 to 50000 1 Units F12 0
070E ANALOG INPUT 4 MAXIMUM –50000 to 50000 1 Units F12 0
MAINTENANCE / TRIP COUNTERS
077F TRIP COUNTERS LAST CLEARED (DATE) N/A N/A N/A F18 N/A
0781 TOTAL NUMBER OF TRIPS 0 to 50000 1 – F1 0
0782 DIGITAL INPUT TRIPS 0 to 50000 1 – F1 0
0783 SEQUENTIAL TRIPS 0 to 50000 1 – F1 0
0784 FIELD-BKR DISCREP. TRIPS 0 to 50000 1 – F1 0
0785 TACHOMETER TRIPS 0 to 50000 1 – F1 0
0786 OFFLINE OVERCURRENT TRIPS 0 to 50000 1 – F1 0
0787 PHASE OVERCURRENT TRIPS 0 to 50000 1 – F1 0
0788 NEG.SEQ. OVERCURRENT TRIPS 0 to 50000 1 – F1 0
0789 GROUND OVERCURRENT TRIPS 0 to 50000 1 – F1 0
078A PHASE DIFFERENTIAL TRIPS 0 to 50000 1 – F1 0
078B UNDERVOLTAGE TRIPS 0 to 50000 1 – F1 0
078C OVERVOLTAGE TRIPS 0 to 50000 1 – F1 0
078D VOLTS/HERTZ TRIPS 0 to 50000 1 – F1 0
078E PHASE REVERSAL TRIPS 0 to 50000 1 – F1 0
078F UNDERFREQUENCY TRIPS 0 to 50000 1 – F1 0
0790 OVERFREQUENCY TRIPS 0 to 50000 1 – F1 0
0791 NEUTRAL O/V (FUND) TRIPS 0 to 50000 1 – F1 0
0792 NEUTRAL U/V (3rd) TRIPS 0 to 50000 1 – F1 0
0793 REACTIVE POWER TRIPS 0 to 50000 1 – F1 0
0794 REVERSE POWER TRIPS 0 to 50000 1 – F1 0
0795 LOW FORWARD POWER TRIPS 0 to 50000 1 – F1 0
0796 STATOR RTD TRIPS 0 to 50000 1 – F1 0
0797 BEARING RTD TRIPS 0 to 50000 1 – F1 0
0798 OTHER RTD TRIPS 0 to 50000 1 – F1 0
0799 AMBIENT RTD TRIPS 0 to 50000 1 – F1 0
079A THERMAL MODEL TRIPS 0 to 50000 1 – F1 0
079B INADVERTENT ENERG. TRIPS 0 to 50000 1 – F1 0
079C ANALOG INPUT 1 TRIPS 0 to 50000 1 – F1 0
079D ANALOG INPUT 2 TRIPS 0 to 50000 1 – F1 0
079E ANALOG INPUT 3 TRIPS 0 to 50000 1 – F1 0
079F ANALOG INPUT 4 TRIPS 0 to 50000 1 – F1 0
MAINTENANCE / GENERAL COUNTERS
07A0 NUMBER OF BREAKER OPERATIONS 0 to 50000 1 – F1 0
Table 6–1: 489 MEMORY MAP (Sheet 7 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39