489 Generator Management Relay 6-19
6 COMMUNICATIONS 6.3 MEMORY MAP
6
1138 CLEAR BREAKER INFORMATION 0 to 1 1 F103 0
SYSTEM SETUP / CURRENT SENSING
1180 PHASE CT PRIMARY 10 to 50001 1 Amps F1 50001
1181 GROUND CT 0 to 3 1 F104 0
1182 GROUND CT RATIO 10 to 10000 1 : 1 / :5 F1 100
SYSTEM SETUP / VOLTAGE SENSING
11A0 VT CONNECTION TYPE 0 to 2 1 F106 0
11A1 VOLTAGE TRANSFORMER RATIO 100 to 30000 1 : 1 F3 500
11A2 NEUTRAL V.T. RATIO 100 to 24000 1 : 1 F3 500
11A3 NEUTRAL VOLTAGE TRANSFORMER 0 to 1 1 F103 0
SYSTEM SETUP / GEN. PARAMETERS
11C0 GENERATOR RATED MVA 50 to 2000001 1 MVA F13 2000001
11C2 GENERATOR RATED POWER FACTOR 5 to 100 1 F3 100
11C3 GENERATOR VOLTAGE PHASE-PHASE 100 to 30001 1 V F1 30001
11C4 GENERATOR NOMINAL FREQUENCY 0 to 3 1 Hz F107 0
11C5 GENERATOR PHASE SEQUENCE 0 to 2 1 F124 0
SYSTEM SETUP / SERIAL START/STOP
11E0 SERIAL START/STOP INITIATION 0 to 1 1 F105 0
11E1 STARTUP INITIATION RELAYS (2-5) 1 to 4 1 F50 0
11E2 SHUTDOWN INITIATION RELAYS (1-4) 0 to 3 1 F50 0
11E3 SERIAL START/STOP EVENTS 0 to 1 1 F105 0
DIGITAL INPUTS / BREAKER STATUS
1200 BREAKER STATUS 0 to 1 1 F209 1
DIGITAL INPUTS / GENERAL INPUT A
1210 ASSIGN DIGITAL INPUT 0 to 7 1 F210 0
1211 ASSERTED DIGITAL INPUT STATE 0 to 1 1 F131 0
1212 INPUT NAME 0 to 12 1 F22 _
1218 BLOCK INPUT FROM ONLINE 0 to 5000 1 s F1 0
1219 GENERAL INPUT A CONTROL 0 to 1 1 F105 0
121A PULSED CONTROL RELAY DWELL TIME 0 to 250 1 s F2 0
121B ASSIGN CONTROL RELAYS (1-5) 0 to 4 1 F50 0
121C GENERAL INPUT A CONTROL EVENTS 0 to 1 1 F105 0
121D GENERAL INPUT A ALARM 0 to 2 1 F115 0
121E ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
121F GENERAL INPUT A ALARM DELAY 1 to 50000 1 s F2 50
1220 GENERAL INPUT A ALARM EVENTS 0 to 1 1 F105 0
1221 GENERAL INPUT A TRIP 0 to 2 1 F115 0
1222 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
1223 GENERAL INPUT A TRIP DELAY 1 to 50000 1 s F2 50
DIGITAL INPUTS / GENERAL INPUT B
1230 ASSIGN DIGITAL INPUT 0 to 7 1 F210 0
1231 ASSERTED DIGITAL INPUT STATE 0 to 1 1 F131 0
1232 INPUT NAME 0 to 12 1 F22 _
1238 BLOCK INPUT FROM ONLINE 0 to 5000 1 s F1 0
1239 GENERAL INPUT B CONTROL 0 to 1 1 F105 0
123A PULSED CONTROL RELAY DWELL TIME 0 to 250 1 s F2 0
123B ASSIGN CONTROL RELAYS (1-5) 0 to 4 1 F50 0
123C GENERAL INPUT B CONTROL EVENTS 0 to 1 1 F105 0
123D GENERAL INPUT B ALARM 0 to 2 1 F115 0
123E ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
123F GENERAL INPUT B ALARM DELAY 1 to 50000 1 s F2 50
1240 GENERAL INPUT B ALARM EVENTS 0 to 1 1 F105 0
1241 GENERAL INPUT B TRIP 0 to 2 1 F115 0
Table 6–1: 489 MEMORY MAP (Sheet 9 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39