489 Generator Management Relay 6-29
6 COMMUNICATIONS 6.3 MEMORY MAP
6
213A ZONE 2 ANGLE 50 to 85 1 ° F1 75
213B ZONE 2 TRIP DELAY 0 to 1500 1 s F2 20
POWER ELEMENTS / REACTIVE POWER
2200 BLOCK Mvar ELEMENT FROM ONLINE 0 to 5000 1 s F1 1
2201 REACTIVE POWER ALARM 0 to 2 1 F115 0
2202 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2203
POSITIVE Mvar ALARM LEVEL
3
2 to 201 1 x rated F14 85
2205
NEGATIVE Mvar ALARM LEVEL
3
2 to 201 1 x rated F14 85
2207 NEGATIVE Mvar ALARM DELAY 2 to 1200 1 s F2 10
2208 REACTIVE POWER ALARM EVENTS 0 to 1 1 F105 0
2209 REACTIVE POWER TRIP 0 to 2 1 F115 0
220A ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
220B
POSITIVE Mvar TRIP LEVEL
3
2 to 201 1 Mvar F14 80
220D
NEGATIVE Mvar TRIP LEVEL
3
2 to 201 1 Mvar F14 80
220F NEGATIVE Mvar TRIP DELAY 2 to 1200 1 s F2 10
2210 POSITIVE Mvar TRIP DELAY 2 to 1200 1 s F2 200
2211 POSITIVE Mvar ALARM DELAY 2 to 1200 1 s F2 100
POWER ELEMENTS / REVERSE POWER
2240 BLOCK REVERSE POWER FROM ONLINE 0 to 5000 1 s F1 1
2241 REVERSE POWER ALARM 0 to 2 1 F115 0
2242 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2243 REVERSE POWER ALARM LEVEL 2 to 99 1
×
Rated F14 5
2245 REVERSE POWER ALARM DELAY 2 to 1200 1 s F2 100
2246 REVERSE POWER ALARM EVENTS 0 to 1 1 F105 0
2247 REVERSE POWER TRIP 0 to 2 1 F115 0
2248 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
2249 REVERSE POWER TRIP LEVEL 2 to 99 1
×
Rated F14 5
224B REVERSE POWER TRIP DELAY 2 to 1200 1 s F2 200
POWER ELEMENTS / LOW FORWARD POWER
2280 BLOCK LOW FWD POWER FROM ONLINE 0 to 15000 1 s F1 0
2281 LOW FORWARD POWER ALARM 0 to 2 1 F115 0
2282 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2283 LOW FWD POWER ALARM LEVEL 2 to 99 1
×
Rated MW F14 5
2285 LOW FWD POWER ALARM DELAY 2 to 1200 1 s F2 100
2286 LOW FWD POWER ALARM EVENTS 0 to 1 1 F105 0
2287 LOW FORWARD POWER TRIP 0 to 2 1 F115 0
2288 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
2289 LOW FWD POWER TRIP LEVEL 2 to 99 1
×
Rated MW F14 5
228B LOW FWD POWER TRIP DELAY 2 to 1200 1 s F2 200
RTD TEMPERATURE / RTD TYPES
2400 STATOR RTD TYPE 0 to 3 1 F120 0
2401 BEARING RTD TYPE 0 to 3 1 F120 0
2402 AMBIENT RTD TYPE 0 to 3 1 F120 0
2403 OTHER RTD TYPE 0 to 3 1 F120 0
RTD TEMPERATURE / RTD #1
2420 RTD #1 APPLICATION 0 to 4 1 F121 1
2421 RTD #1 ALARM 0 to 2 1 F115 0
2422 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2423 RTD #1 ALARM TEMPERATURE 1 to 250 1 °C F1 130
2424 RTD #1 ALARM EVENTS 0 to 1 1 F105 0
2425 RTD #1 TRIP 0 to 2 1 F115 0
2426 RTD #1 TRIP VOTING 1 to 12 1 F122 1
Table 6–1: 489 MEMORY MAP (Sheet 19 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT