6-30 489 Generator Management Relay
GE Power Management
6.3 MEMORY MAP 6 COMMUNICATIONS
6
2427 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
2428 RTD #1 TRIP TEMPERATURE 1 to 250 1 °C F1 155
2429 RTD #1 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #2
2460 RTD #2 APPLICATION 0 to 4 1 – F121 1
2461 RTD #2 ALARM 0 to 2 1 – F115 0
2462 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
2463 RTD #2 ALARM TEMPERATURE 1 to 250 1 °C F1 130
2464 RTD #2 ALARM EVENTS 0 to 1 1 – F105 0
2465 RTD #2 TRIP 0 to 2 1 – F115 0
2466 RTD #2 TRIP VOTING 1 to 12 1 – F122 2
2467 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
2468 RTD #2 TRIP TEMPERATURE 1 to 250 1 °C F1 155
2469 RTD #2 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #3
24A0 RTD #3 APPLICATION 0 to 4 1 – F121 1
24A1 RTD #3 ALARM 0 to 2 1 – F115 0
24A2 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
24A3 RTD #3 ALARM TEMPERATURE 1 to 250 1 °C F1 130
24A4 RTD #3 ALARM EVENTS 0 to 1 1 – F105 0
24A5 RTD #3 TRIP 0 to 2 1 – F115 0
24A6 RTD #3 TRIP VOTING 1 to 12 1 – F122 3
24A7 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
24A8 RTD #3 TRIP TEMPERATURE 1 to 250 1 °C F1 155
24A9 RTD #3 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #4
24E0 RTD #4 APPLICATION 0 to 4 1 – F121 1
24E1 RTD #4 ALARM 0 to 2 1 – F115 0
24E2 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
24E3 RTD #4 ALARM TEMPERATURE 1 to 250 1 °C F1 130
24E4 RTD #4 ALARM EVENTS 0 to 1 1 – F105 0
24E5 RTD #4 TRIP 0 to 2 1 – F115 0
24E6 RTD #4 TRIP VOTING 1 to 12 1 – F122 4
24E7 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
24E8 RTD #4 TRIP TEMPERATURE 1 to 250 1 °C F1 155
24E9 RTD #4 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #5
2520 RTD #5 APPLICATION 0 to 4 1 – F121 1
2521 RTD #5 ALARM 0 to 2 1 – F115 0
2522 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
2523 RTD #5 ALARM TEMPERATURE 1 to 250 1 °C F1 130
2524 RTD #5 ALARM EVENTS 0 to 1 1 – F105 0
2525 RTD #5 TRIP 0 to 2 1 – F115 0
2526 RTD #5 TRIP VOTING 1 to 12 1 – F122 5
2527 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
2528 RTD #5 TRIP TEMPERATURE 1 to 250 1 °C F1 155
2529 RTD #5 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #6
2560 RTD #6 APPLICATION 0 to 4 1 – F121 1
2561 RTD #6 ALARM 0 to 2 1 – F115 0
2562 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
2563 RTD #6 ALARM TEMPERATURE 1 to 250 1 °C F1 130
2564 RTD #6 ALARM EVENTS 0 to 1 1 – F105 0
Table 6–1: 489 MEMORY MAP (Sheet 20 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39