6-32 489 Generator Management Relay
GE Power Management
6.3 MEMORY MAP 6 COMMUNICATIONS
6
26A3 RTD #11 ALARM TEMPERATURE 1 to 250 1 °C F1 80
26A4 RTD #11 ALARM EVENTS 0 to 1 1 – F105 0
26A5 RTD #11 TRIP 0 to 2 1 – F115 0
26A6 RTD #11 TRIP VOTING 1 to 12 1 – F122 11
26A7 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
26A8 RTD #11 TRIP TEMPERATURE 1 to 250 1 °C F1 90
26A9 RTD #11 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / RTD #12
26E0 RTD #12 APPLICATION 0 to 4 1 – F121 3
26E1 RTD #12 ALARM 0 to 2 1 – F115 0
26E2 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
26E3 RTD #12 ALARM TEMPERATURE 1 to 250 1 °C F1 60
26E4 RTD #12 ALARM EVENTS 0 to 1 1 – F105 0
26E5 RTD #12 TRIP 0 to 2 1 – F115 0
26E6 RTD #12 TRIP VOTING 1 to 12 1 – F122 12
26E7 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 – F50 1
26E8 RTD #12 TRIP TEMPERATURE 1 to 250 1 °C F1 80
26E9 RTD #12 NAME 0 to 8 1 – F22 _
RTD TEMPERATURE / OPEN RTD SENSOR
2720 OPEN RTD SENSOR ALARM 0 to 2 1 – F115 0
2721 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
2722 OPEN RTD SENSOR ALARM EVENTS 0 to 1 1 – F105 0
RTD TEMPERATURE / RTD SHORT/LOW TEMP
2740 RTD SHORT/LOW TEMP ALARM 0 to 2 1 – F115 0
2741 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 – F50 16
2742 RTD SHORT/LOW TEMP ALARM EVENTS 0 to 1 1 – F105 0
THERMAL MODEL / MODEL SETUP
2800 ENABLE THERMAL MODEL 0 to 1 1 – F103 0
2801 OVERLOAD PICKUP LEVEL 101 to 125 1
×
FLA F3 101
2802 UNBALANCE BIAS K FACTOR 0 to 12 1 – F1 0
2803 COOL TIME CONSTANT ONLINE 0 to 500 1 min F1 15
2804 COOL TIME CONSTANT OFFLINE 0 to 500 1 min F1 30
2805 HOT/COLD SAFE STALL RATIO 1 to 100 1 – F3 100
2806 ENABLE RTD BIASING 0 to 1 1 – F103 0
2807 RTD BIAS MINIMUM 0 to 250 1 °C F1 40
2808 RTD BIAS CENTER POINT 0 to 250 1 °C F1 130
2809 RTD BIAS MAXIMUM 0 to 250 1 °C F1 155
280A SELECT CURVE STYLE 0 to 2 1 – F142 0
280B STANDARD OVERLOAD CURVE NUMBER 1 to 15 1 – F1 4
280C TIME TO TRIP AT 1.01
×
FLA 5 to 999999 1 s F10 5
280E TIME TO TRIP AT 1.05
×
FLA 5 to 999999 1 s F10 5
2810 TIME TO TRIP AT 1.10
×
FLA 5 to 999999 1 s F10 5
2812 TIME TO TRIP AT 1.20
×
FLA 5 to 999999 1 s F10 5
2814 TIME TO TRIP AT 1.30
×
FLA 5 to 999999 1 s F10 5
2816 TIME TO TRIP AT 1.40
×
FLA 5 to 999999 1 s F10 5
2818 TIME TO TRIP AT 1.50
×
FLA 5 to 999999 1 s F10 5
281A TIME TO TRIP AT 1.75
×
FLA 5 to 999999 1 s F10 5
281C TIME TO TRIP AT 2.00
×
FLA 5 to 999999 1 s F10 5
281E TIME TO TRIP AT 2.25
×
FLA 5 to 999999 1 s F10 5
2820 TIME TO TRIP AT 2.50
×
FLA 5 to 999999 1 s F10 5
2822 TIME TO TRIP AT 2.75
×
FLA 5 to 999999 1 s F10 5
2824 TIME TO TRIP AT 3.00
×
FLA 5 to 999999 1 s F10 5
2826 TIME TO TRIP AT 3.25
×
FLA 5 to 999999 1 s F10 5
Table 6–1: 489 MEMORY MAP (Sheet 22 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39