489 Generator Management Relay 6-33
6 COMMUNICATIONS 6.3 MEMORY MAP
6
2828 TIME TO TRIP AT 3.50
×
FLA 5 to 999999 1 s F10 5
282A TIME TO TRIP AT 3.75
×
FLA 5 to 999999 1 s F10 5
282C TIME TO TRIP AT 4.00
×
FLA 5 to 999999 1 s F10 5
282E TIME TO TRIP AT 4.25
×
FLA 5 to 999999 1 s F10 5
2830 TIME TO TRIP AT 4.50
×
FLA 5 to 999999 1 s F10 5
2832 TIME TO TRIP AT 4.75
×
FLA 5 to 999999 1 s F10 5
2834 TIME TO TRIP AT 5.00
×
FLA 5 to 999999 1 s F10 5
2836 TIME TO TRIP AT 5.50
×
FLA 5 to 999999 1 s F10 5
2838 TIME TO TRIP AT 6.00
×
FLA 5 to 999999 1 s F10 5
283A TIME TO TRIP AT 6.50
×
FLA 5 to 999999 1 s F10 5
283C TIME TO TRIP AT 7.00
×
FLA 5 to 999999 1 s F10 5
283E TIME TO TRIP AT 7.50
×
FLA 5 to 999999 1 s F10 5
2840 TIME TO TRIP AT 8.00
×
FLA 5 to 999999 1 s F10 5
2842 TIME TO TRIP AT 10.0
×
FLA 5 to 999999 1 s F10 5
2844 TIME TO TRIP AT 15.0
×
FLA 5 to 999999 1 s F10 5
2846 TIME TO TRIP AT 20.0
×
FLA 5 to 999999 1 s F10 5
2848 MINIMUM ALLOWABLE VOLTAGE 70 to 95 1 % F1 80
2849 STALL CURRENT @ MIN VOLTAGE 200 to 1500 1
×
FLA F3 480
284A SAFE STALL TIME @ MIN VOLTAGE 5 to 9999 1 s F2 200
284B ACCEL. INTERSECT @ MIN VOLT 200 to 1500 1
×
FLA F3 380
284C STALL CURRENT @ 100% VOLTAGE 200 to 1500 1
×
FLA F3 600
284D SAFE STALL TIME @ 100% VOLTAGE 5 to 9999 1 s F2 100
284E ACCEL. INTERSECT @ 100% VOLT 200 to 1500 1
×
FLA F3 500
THERMAL MODEL / THERMAL ELEMENTS
2900 THERMAL MODEL ALARM 0 to 2 1 F115 0
2901 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2902 THERMAL ALARM LEVEL 10 to 100 1 %Used F1 75
2903 THERMAL MODEL ALARM EVENTS 0 to 1 1 F105 0
2904 THERMAL MODEL TRIP 0 to 2 1 F115 0
2905 ASSIGN TRIP RELAYS (1-4) 0 to 3 1 F50 1
MONITORING / TRIP COUNTER
2A00 TRIP COUNTER ALARM 0 to 2 1 F115 0
2A01 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A02 TRIP COUNTER ALARM LEVEL 1 to 50000 1 Trips F1 25
2A03 TRIP COUNTER ALARM EVENTS 0 to 1 1 F105 0
MONITORING / BREAKER FAILURE
2A20 BREAKER FAILURE ALARM 0 to 2 1 F115 0
2A21 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A22 BREAKER FAILURE LEVEL 5 to 2000 1
×
CT F3 100
2A23 BREAKER FAILURE DELAY 10 to 1000 10 ms F1 100
2A24 BREAKER FAILURE ALARM EVENTS 0 to 1 1 F105 0
MONITORING / TRIP COIL MONITOR
2A30 TRIP COIL MONITOR ALARM 0 to 2 1 F115 0
2A31 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A32 TRIP COIL MONITOR ALARM EVENTS 0 to 1 1 F105 0
MONITORING / VT FUSE FAILURE
2A50 VT FUSE FAILURE ALARM 0 to 2 1 F115 0
2A51 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 F50 16
2A52 VT FUSE FAILURE ALARM EVENTS 0 to 1 1 F105 0
MONITORING / CURRENT DEMAND
2A60 CURRENT DEMAND PERIOD 5 to 90 1 min F1 15
2A61 CURRENT DEMAND ALARM 0 to 2 1 A F115 0
2A62 ASSIGN ALARM RELAYS (2-5) 1 to 4 1 A F50 16
Table 6–1: 489 MEMORY MAP (Sheet 23 of 29)
ADDR NAME RANGE STEP UNITS FORMAT DEFAULT
1, 2, 3 See Table footnotes on page 6–39