CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS DEVICE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5–11
SETPOINT ACCESS
This setting is only available to Administrator. The setpoint access is used for the purpose
of bypassing security. It can be either switched on or assigned to a digital input. If assigned
to a digital input, the digital input needs to be activated through a physical key.
NOTE
NOTE:
If the maximum number of Observer roles already logged in on the relay has been
reached, you must log in on the Security screen within one minute of making the
connection otherwise your session is terminated.
FACTORY SERVICE MODE
When the factory service mode feature is enabled, the device may go into factory service
mode. The default value is Disabled.
REQUIRE PW FOR RESET KEY
This setting is only available to the Administrator. The Require PW for Reset Key is used for
the purpose of bypassing security. If this setting is enabled and an alarm or trip occurs on
the relay, the Reset button is not available to the Operator. Only the Administrator can
reset the relay with their password.
REQUIRE PW FOR D/T CHANGE
The date/time can be set by any role, if this setting is disabled. If this setting is enabled the
date/time can only be set by the Administrator.
REQUIRE PW FOR CONTROL
If this setting is disabled, Operator controls do not require a password. If this setting is
enabled, the Operator password is required. By default Require PW for Control is enabled.
Event Record Description
FAILED AUTH A failed authentication has occurred. Time stamp in UTC
when it occurred is provided.
AUTH LOCKOUT The authentication lockout has occurred because of too
many failed authentication attempts.
LOGIN An event meant to indicate when a certain role logged
in.
LOGOUT An event meant to indicate when a certain role logged
out or timed out.