EasyManua.ls Logo

GE 850 - Remote Inputs

GE 850
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5–94 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
INPUTS CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
Remote Inputs
Remote inputs provide a means of exchanging digital state information between Ethernet-
networked devices supporting IEC 61850. Remote inputs that create FlexLogic operands at
the receiving relay are extracted from GOOSE messages originating in remote devices.
Remote input 1 must be programmed to replicate the logic state of a specific signal from a
specific remote device for local use. The programming is performed by the three settings
shown in the Virtual Inputs section.
Path: Setpoints > Inputs > Remote Inputs
NAME
Range: Up to 13 Alphanumeric Characters
Default: VI 1
An alphanumeric name may be assigned to a Remote Input for diagnostic, setting, and
event recording purposes.
EVENTS
Range: Enabled, Disabled
Default: Enabled
This setting enables event generation whenever Remote Input Status is updated.

Table of Contents

Related product manuals