11–18 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
RTD MAXIMUMS CHAPTER 11: METERING
RTD Maximums
Path: Metering > RTD Maximums
NOTE
NOTE:
The Temperature can be displayed in Celsius or Fahrenheit. The selection is made in
Setpoints > Device > Installation > Temperature Display.
Reset RTD Date/Time
Range: DD/MM/YY hh/mm/ss
NOTE
NOTE:
Maximum RTD values can be cleared (reset) by setting the value of Setpoints > Records >
Clear Records > RTD Maximums to “ON”. Executing this command loads -40°C (or -40°F) as
the initial Maximum RTD value.
RTD 1(13) Max
Range: -40 to 250°C (-40 to 482°F)
Temperatures < -40°C are displayed as “Shorted” and temperatures > 250°C are
displayed as “Open RTD.
RTD 1(13) Max Date/Time
Range: DD/MM/YY hh/mm/ss
RRTD Maximums
Path: Metering > RRTD Maximums
NOTE
NOTE:
The Temperature can be displayed in Celsius or Fahrenheit. The selection is made in
Setpoints > Device > Installation > Temperature Display.
Reset RRTD Date/Time
Range: DD/MM/YY hh/mm/ss
NOTE
NOTE:
Maximum RRTD values can be cleared (reset) by setting the value of Setpoints > Records >
Clear Records > RRTD Maximums to “ON”. Executing this command loads -40°C (or -40°F)
as the initial Maximum RRTD value.
RRTD 1(12) Max
Range: -40 to 250°C (-40 to 482°F)
Temperatures < -40°C are displayed as “Shorted” and temperatures > 250°C are
displayed as “Open RRTD”.
RRTD 1(12) Max Date/Time
Range: DD/MM/YY hh/mm/ss
Analog Inputs
Path: Metering > Analog Inputs
Analog Ip 1 (4)
Range: -500000 to 500000 units in steps of 1