EasyManua.ls Logo

GE 850 - Page 237

GE 850
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS SYSTEM
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5–75
Figure 5-17: Disconnect Switch State Detection logic diagram
SETPOINT
89a CONTACT
FlexLogic operand =1, Off = 0
SETPOINT
89b CONTACT
FlexLogic operand =1, Off = 0
FlexLogic operand
(SW1 89a state)
FlexLogic operand
(SW1 89b state)
AND AND
XOR
PKP
S
R
LED: ALARM
LATCH
OR
AND
OR
OR
ANDAND
FLEXLOGIC OPERANDS
SW1 CLOSED
FLEXLOGIC OPERANDS
SW1 OPENED
FLEXLOGIC OPERANDS
SW1 DISCREPANCY
OR
FLEXLOGIC OPERANDS
SW1 NOT CONFIGURED
SETPOINT
ALARM DELAY
t
Positive
Edge
SETPOINT
RESET ALARM
FlexLogic operand, Off = 0
FLEXLOGIC OPERANDS
SW1 INTERMITTENT
FLEXLOGIC OPERAND
89a CONTACT
FLEXLOGIC OPERAND
89b CONTACT
894193A1.cdr

Table of Contents

Related product manuals