EasyManua.ls Logo

GE 850 - Page 324

GE 850
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6–56 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
CURRENT ELEMENTS CHAPTER 6: PROTECTION SETPOINTS
Figure 6-22: Restricted Ground Fault Protection Logic Diagram
89$1.cdr
SETPOINTS
RGF 1
FUNCTION:
Alarm
Latched Alarm
OR
AND
LED: ALARM /
LATCHED ALARM
Command
AND
S
R
LATCH # 1
Set-
Dominant
Configurable
FlexLogic Operands
RGF 1 OP
SETPOINTS
Do Not Operate, Operate
OUTPUT RELAY 3 (X)
Source IB
Source IC
AND
SETPOINTS
RGF 1
BLOCK :
Off = 0
Source IA
Disabled
OR
RESET
Igd
Imax
Igd >= I pickup
RUN
SETPOINTS
RGF 1
PICKUP DELAY:
t
PKP
0
Select highest value
Imax = max (Ia,Ib,Ic)
Trip
Operate Output Relay 1 (TRIP)
LED: TRIP
AND
Igd = |3Io + Ig|
Calculate 3Io
SETPOINTS
RGF 1
PICKUP:
RGF 1
SLOPE:
Source Ig
>
=
AND
SETPOINTS
RGF 1
GND CURR SUPERV:
Disabled = 0
Enabled = 1
RGF 1 GND CURR
SUPERV LEVEL :
Ig > I Level
OR
AND
RGF 1 PKP
LED: PICKUP
RGF 1 Superv ON
METERING
I0
Ig
Igd
Currents

Table of Contents

Related product manuals