CHAPTER 6: PROTECTION SETPOINTS CURRENT ELEMENTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 6–81
TARGETS
Range: Self-Reset, Latched, Disabled
Default: Self-Reset
The setting is used to define the operation of an element target message. When set to
“Disabled”, no target message is issued upon operation of the element. When set to
“Self-Reset”, the target message and LED indication follow the operate state of the
element, and self-resets once the operate element condition clears. When set to
“Latched”, the target message will remain visible after the element output returns to
logic 0 until a RESET command is received by the relay.