6–140 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
FREQUENCY ELEMENTS CHAPTER 6: PROTECTION SETPOINTS
Figure 6-61: Underfrequency Protection logic diagram
892737A4.cdr
LED: PICKUP
CT INPUT
CT Bank 1 J1
SETPOINTS
BLOCK :
Off=0
AND
SETPOINTS
UNDERFREQ 1
FUNCTION :
Disabled
Trip
Alarm
Latched Alarm
Configurable
OR
Positive -
sequence
SETPOINTS
UNDERFREQ 1
MINIMUM CURRENT :
I MINIMUM
SETPOINTS
UNDERFREQ 1
MINIMUM VOLTAGE :
AND
SETPOINTS
UNDERFREQ 1
PICKUP:
0<fPICKUP
FREQUENCY f
RUN
SETPOINTS
UNDERFREQ 1
PICKUP DELAY :
t
PKP
t
DPO
UNDERFREQ 1
DROPOUT DELAY :
Underfreq1 OP
FlexLogic Operands
Underfreq 1 PKP
AN D AND AND
Command
RESET
OR
LED: ALARM
LED: TRIP
Operate Output Relay 1 (TRIP)
RUN
V MINIMUM
RUN
SETPOINTS
OUTPUT RELAYS 3(X)
Do Not Operate , Operate
S
LATCH
Set-
Dominant
R
SETPOINTS
UNDERFREQ 1
VT INPUT :
Positive -
sequence
Composite
SETPOINTS
Ph VT Bnk 1 J2
wye/delta
Vx