7–48 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
RTD TEMPERATURE CHAPTER 7: MONITORING
ALARM DROPOUT DELAY
Range: 0 s to 600 s in steps of 1 s
Default: 0 s
ALARM OUTPUT RELAY X
For details see Common Setpoints
.
BLOCK
Range: Off, Any FlexLogic operand
Default: Off
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Latched