EasyManua.ls Logo

GE 850 - Page 536

GE 850
664 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
8–64 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
BUS TRANSFER CHAPTER 8: CONTROL
FAST PATH:
The #2 CLOSE OUTPUT relay is blocked if Transfer is enabled, but blocked while the breaker
is connected (racked-in). If breaker closing is required during maintenance, Transfer must
be disabled.
EVENTS
Range: Disabled, Enabled
Default: Enabled
TARGETS
Range: Disabled, Self-reset, Latched
Default: Self-reset
850 RELAY – INCOMER 2
When INCOMER 2 function is selected the following display is available:
INC 2 CB CONNECTED
Range: Off, Any FlexLogic operand
Default: Off
The setpoint selects the FlexLogic operand, digital input, virtual input or remote input
used to inhibit transfer if Incomer breaker 2 cannot be used to pass current from the
source to the load (for example when the breaker is in rack-out or test position). This
setpoint also provides the condition for “Selected to Trip” breaker logic, FlexLogic
operand INC2 CB CON & CLSD required for Incomer 2 Circuit Breaker transfer logic, Bus
Tie Circuit Breaker transfer logic, and for blocking #2 close relay.
FAST PATH:
For non-draw-out breakers without associated disconnect switches, this setpoint must be
set as ON.

Table of Contents

Related product manuals