CHAPTER 8: CONTROL AUTORECLOSE
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 8–89
RAISE PHASE TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
This setpoint determines the characteristics of the PHASE TOC 1/2 protection element by
raising the Pickup level.
RAISE NEUTRAL TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEUTRAL TOC 1/2 protection element
by raising the Pickup level.
RAISE GROUND TOC 1 (2, 3, 4) PKP
Range: 1 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the GROUND TOC 1 protection element by
raising the Pickup level.
RAISE SENS GND TOC 1/2 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the SENSITIVE GROUND TOC 1 protection
element by raising the Pickup level.
RAISE NEG SEQ TOC 1/2 PKP
Range: 0 to 100% in steps of 1%
Default: 0
The setpoint determines the characteristics of the NEGATIVE SEQUENCE TOC 1
protection element by raising the Pickup level.
SELECT SETTING GROUP
Range: Active, Group 1, 2, 3, 4, 5, 6
Default: Group 1
This setpoint determines the setting group that is used for AR1 Reclose Shot 1.
FAST PATH:
The above setpoints are repeated for each of the Reclose shots 1 through 4.