13–2 850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL
ENVIRONMENTAL HEALTH REPORT CHAPTER 13: MAINTENANCE
Environmental Health Report
Prolonged exposure to harsh environments and transient conditions that exceed those
stated in Section 1 - Specifications reduce the life of electronic products. The 850 has an
Environmental Awareness Module (EAM) to record environmental data over the life of the
product. The patented module measures temperature, humidity, surge pulses and
accumulates the events every hour in pre-determined threshold buckets over a period of
15 years. Retrieve this data in the form of a histogram using EnerVista Setup Software to
ensure any change in the operating condition of the installed fleet is identified quickly so
remedial action can be taken.