380–480 V
HP kW
A Input Efficiency
IP00/Chassis IP20/Chassis IP21/Type 1 IP54/IP55/Type 12 IP66/Type 4X
≤ 440 V
>440 V
350 250 480 443 463 0.98
52
44h 42h/51 42h/51
450 315 588 530 590 0.98
51 51500 355 658 590 647 0.98
550 400 745 678 733 0.98
600 450 800 730 787 0.98
61/63 61/63
650 500 880 780 857 0.98
750 560 990 890 964 0.98
900 630 1120 1050 1090 0.98
1,000 710 1260 1160 1227 0.98
62/64 62/64
1200 800 1460 1380 1422 0.98
Table 13.2 380–480 V
525–600 V
HP kW
A Input Efficiency IP20/Chassis IP55/Type 12 IP66/Type 12
≤ 550 V
>550 V
1 0.75 1.8 1.7 1.7 0.97
13 15 15
2 1.5 2.9 2.7 2.7 0.97
3 2.2 4.1 3.9 4.1 0.97
5 4.0 6.4 6.1 5.8 0.97
7.5 5.5 9.5 9 8.6 0.97
10 7.5 11.5 11 10.4 0.97
23 21 2115 11 19 18 17.2 0.98
20 15 23 22 20.9 0.98
25 18 28 27 25.4 0.98
24 22 2230 22 36 34 32.7 0.98
40 30 43 41 39 0.98
50 37 54 52 49 0.98
33 31 31
60 45 65 62 59 0.98
75 55 87 83 79 0.98
34 32 32
100 75 105 100 96 0.98
Table 13.3 525–600 V
525–690 V
HP kW
HP
at
575
V
A Input Efficiency
IP00/Chassis IP20/Chassis IP21/Type 1 IP54/IP55/Type 12
≤ 550 V
>690 V
15 11 11 14 13 15 0.98
22 22
20 15 15 19 18 19.5 0.98
25 18 20 23 22 24 0.98
30 22 25 28 27 29 0.98
40 30 30 36 34 36 0.98
32 32
50 37 40 43 41 49 0.98
60 45 50 54 52 59 0.98
75 55 60 65 62 71 0.98
100 75 75 87 83 87 0.98
Specifications
AF-650 GP
TM
Design and Installation Guide
13-2 DET-767A
133