AF-650 GP 3-phase Recommended fuse size Recommended max fuse
[kW]/[HP]
0.37/1/2
gG-16 gG-25
0.75/1
1.5/2
2.2/3
3.7/5
5.5/7.5
gG-20 gG-32
7.5/10
11/15
gG-50 gG-63
15/20
18.5/25
gG-80 gG-125
22/30
30/40
37/50 gG-125 gG-150
45/60 aR-160 aR-160
55/75
aR-250 aR-250
75/100
90/125 gG-300 gG-300
110/150 gG-350 gG-350
132/200 gG-400 gG-400
160/250 gG-500 gG-500
200/300 gG-630 gG-630
250/350 aR-700 aR-700
315/450
aR-900 aR-900355/500
400/550
450/600
aR-1600 aR-1600
500/650
560/750
aR-2000 aR-2000
630/900
710/1,000
aR-2500 aR-2500
800/1200
Table 13.7 380–480 V, IP20/Open Chassis
Specifications
AF-650 GP
TM
Design and Installation Guide
DET-767A 13-21