AF-650 GP 3-phase Recommended fuse size Recommended max fuse
[kW]/[HP]
11/15 gG-25
gG-63
15/20
gG-32
18.5/25
22/30 gG-40
30/40
gG-63
gG-80
37/50 gG-100
45/60 gG-80 gG-125
55/75 gG-100
gG-160
75/100 gG-125
90/125 aR-250 aR-250
110/150 aR-315 aR-315
132/200
aR-350 aR-350
160/250
200/300 aR-400 aR-400
250/350 aR-500 aR-500
315/400 aR-550 aR-550
355/500
aR-700 aR-700
400/550
500/650
aR-900 aR-900
560/750
630/900
aR-1600 aR-1600
710/1,000
800/1150
900/1250
1,000/1,350 aR-2000 aR-2000
Table 13.11 525–690 V, IP21/Nema 1 and IP55/Nema 12 and IP66/Nema 4X