EasyManuals Logo

GE EST iO500 User Manual

GE EST iO500
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #131 background imageLoading...
Page #131 background image
Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual 121
2 wire Class B: Allows for the monitoring of two-wire conventional smoke detectors in a Class B
circuit (that do not require alarm verification) and normally open contact initiating devices on
the same circuit
2 wire verify Class B: Allows for the monitoring of two-wire conventional smoke detectors in a
Class B circuit (that require alarm verification)
2 wire Class A: Allows for the monitoring of two-wire conventional smoke detectors in a Class A
circuit (that do not require alarm verification) and normally open contact initiating devices on
the same circuit.
2 wire verify Class A: Allows for the monitoring of two-wire conventional smoke detectors in a
Class A circuit (that require alarm verification)
Audible: Assigned to NACs connected to audible notification appliances that turn off when
Signal Silence is pressed
Visible: Assigned to NACs connected to visible notification appliance that do not turn off when
Signal Silence is pressed
Relay module
Relay nonsilence: For the connection of relay devices that do not follow signal silence.
Relay with silence: For the connection of relay devices that follow signal silence.
Loop Configuration
Zone
Correlation Groups
Device
Device
Loop 01<>
Device
Number 001
Loop 01 Device 001
Device 001
Zone 01<>
Label <>
Correlation Groups
To program a device:
1. Access the loop configuration options menu. See "Loop
configuration options."
2. Choose Device.
3. Choose the loop the device is on. Note: If your panel only has
one loop, the loop selection screen does not display. Go to the
next step.
4. Choose the device (address) you want to configure. For the
250/500 point panel, addresses 1 to 125 are detectors and
addresses 126 to 250 are modules.
Note: The two lines below the device number line on the screen
are the device label.
5. Program each device in your system using the "Device
programming options" table above.
Note: If you chose a dual address device, both addresses for
the device are displayed on the screen (e.g. 001/002). The first

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE EST iO500 and is the answer not in the manual?

GE EST iO500 Specifications

General IconGeneral
BrandGE
ModelEST iO500
CategoryControl Panel
LanguageEnglish

Related product manuals