Chapter 1: System operation
44 EST iO64 and iO500 Technical Reference Manual
Enabling a loop event
You can enable a disabled loop event so that it displays on the LCD
display when it activates. When you enable a loop event:
The common Disable LED turns off (if there are no other
disabled loop events)
The common Trouble LED turns off
The disabled points and active points counters on the LCD
display decrement
The message on the LCD display indicating the disabled loop
event disappears
Reports
Test
Control
Program
Enter Password
0000
Control
Enable/Disable
Activate/Restore
Enable/Disable
Zone
Panel Event
Loop Event
To enable a loop event:
1. Press the Menu button.
2. Choose Control.
3. Enter your password (the minimum of a level one password is
required).
4. Choose Enable/Disable.
5. Choose Loop Event.
6. Select the loop event type that you want to enable.
Refer to "Event ID numbers and descriptions" for event
descriptions.
7. Press Enter.
8. Press Cancel to return to the previous menu.
— or —
Press the Menu button to exit menu mode.
Loop Event Enable<>
001
Event 001