EasyManuals Logo

GE EST iO500 User Manual

GE EST iO500
284 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #140 background imageLoading...
Page #140 background image
Chapter 3: Programming
130 EST iO64 and iO500 Technical Reference Manual
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the connected network
CID: Contact ID event code (000 to 999)
Loop Configuration
Loop Class
Zone
Correlation Groups
Zone
Number 01>
Zone 01
Zone 01
Type Alarm<>
Label >
Correlation Groups
To program a zone:
1. Access the loop configuration options menu. See "Loop
configuration options."
2. Choose Zone.
3. Choose the zone (number) you want to configure.
4. Program each zone in your system using the "Zone
programming options" table above.
5. When you finish programming each option, choose Save.
6. Continue programming your system or press Menu to exit menu
mode.
Zone 01
Correlation Groups
Event Notification
Save

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE EST iO500 and is the answer not in the manual?

GE EST iO500 Specifications

General IconGeneral
BrandGE
ModelEST iO500
CategoryControl Panel
LanguageEnglish

Related product manuals