Chapter 3: Programming
EST iO64 and iO500 Technical Reference Manual 157
Common Trouble
Correlation Groups
Event Notification
Correlation Groups
Group 01 No<>
Group 02 No<>
Group 03 No<>
Correlation Groups
Group 31 No<>
Group 32 No<>
Save
Common Trouble
Correlation Groups
Event Notification
Trouble
Printer Yes<>
Code 10-10-10-10
Dialer Account 1&2
15. Set trouble event notification.
Printer: Yes or No. Specifies if event information is printed
Coder: 4-digit coded output, which is played in response to
alarm conditions (00-00-00-00 to 99-99-99-99)
Dialer:
Acct 1 & 2: Event information is sent to both dialer accounts
Acct 1: Event information is sent to dialer account one
Acct 2: Event information is sent to dialer account two
None: Event information is not sent to the dialer
NET: Yes or No. Specifies if event information is sent to the
connected network
CID: Contact ID event code (000 to 999)
16. When finished, choose Save.
17. Continue programming your system or press Menu to exit menu
mode.
Trouble
NET Yes
CID 110
Save