Appendix E: Device types to personality codes correlation
266 EST iO64 and iO500 Technical Reference Manual
Model name Device type Personality code
UM Supervised Output Class A (15) Signal - supervised output (Class A)
UM Continuous Non-Silenceable Class
A
(15) Signal - supervised output (Class A)
UM Continuous Silenceable Class A (15) Signal - supervised output (Class A)
UM Continuous Non-Silenceable (16) Signal - supervised output (Class B)
UM Continuous Silenceable (16) Signal - supervised output (Class B)
MAB Smoke (1) Alarm - NO latching (Class B)
MAB Heat (1) Alarm - NO latching (Class B)
MAB Pull Station (1) Alarm - NO latching (Class B)
MAB Water Flow (2) Alarm - NO delayed latching (Class B)
MAB Supervisory Latching (4) Active - NO latching (Class B)
MAB Supervisory Nonlatching (3) Active - NO nonlatching (Class B)
MAB Monitor (3) Active - NO nonlatching (Class B)
MAB Remote Reset (3) Active - NO nonlatching (Class B)
MAB Remote Drill (3) Active - NO nonlatching (Class B)
MAB Remote Signal Silence (3) Active - NO nonlatching (Class B)
MAB Remote AC Fail (3) Active - NO nonlatching (Class B)
MAB Alarm (1) Alarm - NO latching (Class B)
MAB 2-Wire Alarm (13) Alarm - two-wire smoke unverified (Class B)
MAB 2-Wire Alarm Verify (14) Alarm - two-wire smoke verified (Class B)
MAB 2-Wire Alarm Class A (20) Alarm - two-wire smoke unverified (Class A)
MAB 2-Wire Alarm Verify Class A (21) Alarm - two-wire smoke verified (Class A)
MAB Alarm Class A (9) Alarm - NO latching (Class A)
MAB Pull Station Class A (9) Alarm - NO latching (Class A)
MAB Heat Class A (9) Alarm - NO latching (Class A)
MAB Smoke Class A (9) Alarm - NO latching (Class A)
MAB Water Flow Class A (10) Alarm - NO delayed latching (Class A)
MAB Supervisory Latching Class A (12) Active - NO latching (Class A)
MAB Supervisory Nonlatching Class A (11) Active - NO nonlatching (Class A)
MAB Monitor Class A (11) Active - NO nonlatching (Class A)
MAB Remote AC Fail Class A (11) Active - NO nonlatching (Class A)
MAB None (0) No Personality
MAB Supervised Output (16) Signal - supervised output (Class B)
MAB Supervised Output Class A (15) Signal - supervised output (Class A)
MAB Continuous Non-Silenceable Class
A
(15) Signal - supervised output (Class A)
MAB Continuous Silenceable Class A (15) Signal - supervised output (Class A)
MAB Continuous Non-Silenceable (16) Signal - supervised output (Class B)